POTTER & BRUMFIELD W28 series SWITCHABLE OR PUSH TO RESET FUSEHOLDER-TYPE THERMAL CIRCUIT BREAKER FEATURES · Switchable version combines on-off switch and circuit protection in a single unit. · Approved to many international standards (push to reset type). · Replaces slow blow glass cartridge fuse. · Labor-saving snap-in mounting. · Button extends for visual trip indication on push to reset model. · Rocker on switchable model moves to "overload" position upon trip. Calibration: Will continuously carry 100% of rating. 3-20A models - may trip between 101% and 134%, but must trip at 135% of rating within one hour at +25C. 0.25-2A models - may trip between 101% and 174%, but must trip at 175% of rating within one hour at +25C. Dielectric Strength: Over 1,500 volts RMS. Maximum Operating Voltages: 32VDC; 250VAC, 50/60 Hz. Interrupt Capacity: 1,000A at 250VAC, 50/60 Hz. and 32VDC in accordance with UL standard 1077. Resettable Overload Capacity: Six times rated current for 0.25A through 2A models. Ten times rated current for 3 - 20A models. Reset Time: 180 seconds max. for 0.25A through 2A models. 10 to 60 seconds for 3 through 20A models. Endurance Cycling (switchable type): Typically 30,000 operations at 100% of rating. Termination: .250" (6.35mm) quick connects. Soldering to terminals is not recommended. Mounting: Snaps into panel from front. See Recommended Panel Cutouts (not shown). Approx Weight: 0.35oz (10g). (approx. 47 .jpg @ 780 pixels wide). BUILD YOUR OWN PART NUMBER: A 49K graphic (jpg) of Ordering Information. This information will 'build' a part number from a list of available specifications. |
Call: 414-327-1555 Fax : 414-327-0577 Email: indelect@execpc.com Catalog, Quote, Availability. © 2007 Industrial Electronics By Ross LLC |