· Industry standard octal-type termination for quick installation. · Contact arrangements from 1 Form A (SPST - NO) to 3 Form C (SPDT). · Indicator lamp and push-to-test options available on certain models. · The KRPA series is the automated manufactured version of the KRP series. · Hermetically sealed option available with KR UL recognized for Class I · Div. 2 Hazardous locations, Groups A, B, C, D.
Arrangements: See Ordering Information Table.
Materials: Silver or silver-cadmium oxide, with or without gold
flashing.
Expected Life: 10 million operations min., mechanical; 100,000
operations min. @ rated loads.
(KR not UL Rated)
Contact
Code Arrangement Contact Rating
Y&L 1, 2, 3 Poles 5A @ 120VAC
(Silver) 3A @ 240VAC
1/10HP @ 120VAC
1/6 HP @ 240VAC
G&N 1, 2, 3 Poles 10A @ 240VAC
(Silver-Cad. 1/2 HP @ 240VAC
Oxide) 1/3 HP @ 120VAC
Contact
Code Arrangement Contact Rating
Y&L 1,2,3 Poles 5A @ 28VDC, 120VAC, 80% PF
G&N 1,2,3 Poles 10A @ 28VDC, 120VAC, 80% PF
6A @ 250VAC
Contact
Code Series Contact Rating
Y KA (1) 5A @ 120VAC, 3A @ 240VAC,
1/10 HP @ 120VAC, 1/6 HP @ 240VAC
G KA (2) 10A @ 120VAC, 6A @ 240VAC
1/6 HP @ 120VAC, 1/3 HP @ 240VAC
Notes:
1 Listed by C.S.A. for 5A @ 120VAC 80% PF
2 Listed by C.S.A. for 10A @IPOVAC 80% Pr
Between Open Contacts: 500V rms Between All Contacts: 1,500V rms
Nominal Power Maximum Power
KRP AC 2VA Open Models - 5VA
Enclosed Models-4VA
KRPA DC 1.2W Open Models - 4W
Enclosed Models - 3W
KA AC 2VA
DC 125mW/movable arm Open Models -4W
Notes:
Duty Cycle: Continuous.
Initial Insulation Resistance: KRP, KRPA - 1000 Megohms, min.
KA - 100 Megohms, min.
Nominal DC Ohms Nominal Coil
Voltage +/-10% Current (ma)
6 32 188
12 120 100
DC 24 472 51
Coils 48 1,800 26.6
110 10,000 11.5
220 Use 110V relay with 10,000 Ohm 5W Resistor in series
6 6 335
AC 12 24 168
Coils 24 85 84
120 2,250 17.5
240 9,110 8.75
Must-Operate Voltage: DC: 75% of nominal voltage.
AC: 85% of nominal voltage.
Operate Time (Excluding Bounce):
15 milliseconds typical @ nominal voltage
Release Time (Excluding Bounce):
10 milliseconds typical @ nominal voltage
Temperature Range:
Open Models: AC: -45 degree C to +70 degree C
DC: -45 degree C to +85 degree C
Enclosed Models: AC: -45 degree C to +55 degree C
DC: -45 degree C to +70 degree C
Open Models: Solder Terminals.
Enclosed Models: Octal-Type Plug.
Enclosures: Transparent Polycarbonate.
Hermetically sealed metal case.
Also available with KR.
Weight: KA: 1.7 oz. (48.2 g) approximately.
KRPA, KRP: 3.0 oz. (85 g) approximately.
(approx. 86 and 79K .gifs @ 750 pixels wide). BUILD YOUR OWN PART NUMBER: A 47K graphic (GIF) of Ordering Information. This information will 'build' a part number from a list of available specifications. |
![]() |