POTTER & BRUMFIELD PRD series 10 to 50 AMP HEAVY DUTY AC OR DC POWER RELAY File E22575 (Models With All Screw Terminals) File E22575 (All Others) File 15734 · Contact ratings to 50 amps. · Magnetic blowouts available for switching DC loads · Arrangements to DPDT. · SPDT auxiliary switch available. · Replaces PR series. Arrangements: Available to 2 Form C (DPDT). See ordering information table. Ratings: See UL contact rating table. Material: Silver and silver-cadmium oxide standard. Other materials available for special applications. Expected Life: 100,000 operations at rated loads @25"C. Contact life increases at reduced loads or with appropriate arc suppression. Type Supply Contact Ratings AC or DC PRD 1, 2, 3 25 amps at 277VAC 4, 5, 6 AY DY 1 HP at 120VAC 2 HP at 250VAC 10 amps at 600VAC 7 amps at 50VDC Res. PRD 1, 2, 3 30 amps at 277VAC Res. 4, 5, 6 AG DG 1.5 HP at 120VAC 2 HP at 250VAC 10 amps at 6OOVAC PRD 7, 8 or 11 25 amps at 240VAC AY DY 20 amps at 277VAC 1 HP at 120VAC 2 HP at 250VAC 7 amps at 50VDC Res. 10 amps at 6OOVAC PRD 7, 8 or 11 30 amps at 240VAC AG DG 20 amps at 277VAC 1.5 HP at 120VAC 2 HP at 250VAC 10 amps at 600VAC PRD 3,7, 8 or 11 AH DH 20 amp at 125VDC AJ DJ 1/3 HP at 125VDC Type Contact Ratings Minimum Life 50 Amps. 277VAC max., General Purpose 100,000 Cycles PRD3AP4 30 Amps. 277VAC max., Ballast 6,000 Cycles PRD3DP4 15 Amps. 277VAC max., Tungsten 6,000 Cycles 102 LRA, 17 FLA, 240VAC 30,000 Cycles 120 LRA, 20 FLA, 120VAC 30,000 Cycles 1.5 HP at 120VAC 30,000 Cycles 3 HP at 240VAC 30,000 CyclesNote: Any PRD relay deviating electrically or physically from the standard models in the table is not UL or CSA listed. All horsepower ratings are for single phase motors Type Contact Ratings PRD3AR4 60 Amps, 28VDC Res. PRD3DR4 30 Amps, 125VDC Res. Arrangements: 1 Form C (SPDT). Rating: 5 amps at I20VAC, 60 Hz. @ 25 Degree C. Material: Silver. Initial Breakdown Voltage: 2,000V rms minimum between all elements and ground. (2,200V rms on 600V ratings.) Voltage: From 6 to 220VDC, and 6 to 480VAC. Resistance: See coil data table. Nom. Power: DC coils: - 2.0 watts @ 25 degree C. AC coils: - 9.8 VA @ 25 degree C. Max Power: DC coils: - 8.0 watts @ 25 degree C. Duty Cycle: Continuous. Initial Insulation Resistance: 100 megohms, minimum. "DY" AND "DG" "AY" AND "AG" DC COILS AC COILS (50-60HZ.) Nominal Res. Nominal Resistance Nominal DC Nom. DC Resis. Nominal AC Volts In Ohms Current In Volts In Ohms CurrentIn +/-10%@25C Milliamps +/-15%@25"C Milliamps 6 18 333 6 .86 1600 12 71 169 12 3.2 820 24 288 84 24 72.0 410 110 6050 18.2 120 290 85 220 use 110V relay with 240 1200 43 approx. 6 ,000 ohm 480 4500 22 5W wire-wound Must-Operate Voltage: DC: 75% of nominal voltage @ 25C AC: 85% of nominal voltage @ 25C Temperature Range: AC: -55 Degree C to +45 Degree C DC: -55 Degree C to +80 Degree C Mounting: Two .187" (4.75mm) diameter holes on 1.875" (47.63 mm) centers. Termination: See ordering information tables for various options. Insulating Material: Molded phenolic. Enclosure: Metal dust cover, 35D013, available. Order separately. Weight: 10 oz. (284g) approximately. (approx. 65K .gif @ 750 pixels wide). BUILD YOUR OWN PART NUMBER: A 57K graphic (GIF) of Ordering Information. This information will 'build' a part number from a list of available specifications. |
Call: 414-327-1555 Fax : 414-327-0577 Email: indelect@execpc.com Catalog, Quote, Availability. © 2007 Industrial Electronics By Ross LLC |