Over/Under Voltage Relays provide protection to equipment where an over or under voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value. The pick-up voltage setting is user-adjustable from 85-115% of the nominal voltage rating. As standard, the VAP Series has a drop-out voltage setting fixed at 95% of the pick-up voltage setting. An adjustable drop-out setting of 75-95% of the pick-up setting is available on the VAKP Series. The relay energizes when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (T), which is adjustable from 0.5-10 seconds for VA Series products. A time delay on drop-out fixed at 500ms is available (see VA Series). |
|
|
NOMINAL VOLTAGE | PICK-UP VOLTAGE RANGE | DROP-OUT VOLTAGE RANGE | PRODUCT NUMBER | WIRING/SOCKET | ||
24VAC 120VAC |
21-27VAC 102-138VAC |
20-26V AC 99-131V AC |
VAP024A VAP120A |
8 Pin Octal 70169-D DIAGRAM 20 |
||
12VDC 24VDC 48VDC 110VDC |
10-14VDC 21-27VDC 41-55VDC 94-126VDC |
9-13V DC 20-26V DC 39-52V DC 89-121V DC |
VAP012D VAP024D VAP048D VAP110D |
|||
Drop-Out Voltage is fixed at 95% of the Pick-Up Setting. Click here for Sockets & Accessories. | ||||||
NOMINAL VOLTAGE | PICK-UP VOLTAGE RANGE | DROP-OUT VOLTAGE RANGE | PRODUCT NUMBER | WIRING/SOCKET | ||
24VAC 120VAC |
21-27VAC 102-138VAC |
16-26V AC 77-131V AC |
VAKP024A VAKP120A |
8 Pin Octal 70169-D DIAGRAM 20 |
||
12VDC 24VDC 48VDC 110VDC |
10-14VDC 21-27VDC 41-55VDC 94-126VDC |
8-13V DC 16-26V DC 32-52V DC 71-121V DC |
VAKP012D VAKP024D VAKP048D VAKP110D |
|||
** Drop-Out Voltage is adjustable from 75-95% of the Pick-Up Setting. Click here for Sockets & Accessories. | ||||||
Operating ModesVoltage Monitoring Relays can be used as either overvoltage or undervoltage relays, depending on the output contact used: | |
Overvoltage Relay
Provides protection to equipment that cannot handle excess voltages. Uses a normally closed contact (N.C.). As long as the monitored voltage remains below the maximum voltage the equipment can withstand (Pick-Up Setting), the relay remains de-energized and the N.C. contact remains closed, keeping the load energized. If the operating voltage increases beyond the maximum rating of the equipment, the relay energizes and the N.C. contact opens, turning off the load. When the voltage falls below the Drop-Out Setting (hysteresis), the relay de-energizes and the N.C. contact re-closes, turning on the load. |
Undervoltage Relay
Provides protection to equipment that is required to operate above a certain minimum voltage. Uses a normally open contact (N.O.). As long as the monitored voltage is above the minimum value required (Pick-Up Setting), the relay will energize and the N.O. contact closes, turning on the load. If the voltage drops below the Drop-out Setting (the minimum voltage required minus the hysteresis), the relay will de-energize and the N.O. contact will re-open, turning off the load. |
Application DataVoltage Monitoring Relays can be used as either overvoltage or undervoltage relays, depending on the output contact used: | |
Voltage Tolerance +25%/-50% of nominal voltage; AC voltages are 50-60Hz; No supply (input) voltage is required. Load (Burden): 3VA. Voltage Settings Pick-up: Adjustable from 85-115% of nominal voltage Drop-out: Fixed at 95% of the pick-up setting (VAP Series) Adjustable from 75-95% of pick-up setting (VAKP Series) Temperature: -28o to 65oC (-20o to 150oF) Output Contacts: 10A Resistive @ 240VAC/30VDC, 1/2HP @ 240VAC (N.O.), 1/3HP @ 240VAC (N.C.) Life: Mechanical: 10,000,000 operations Full Load: 100,000 operations |
Response Times: Operate: 500ms Release:Adjustable from 0.5 - 10 Seconds Indicator LED: Red when Relay is energized and Green when Relay is Off. Transient Protection: 10,000 volts for 20 microseconds Reset: Automatic Approvals: |