Description: Current-Limiting, Fast-acting (1⁄2-6A), time-delay (7-60A)fuse.
Ratings:
Volts: 600Vac (1⁄2-20A); 480Vac (25-60A); 170Vdc (1⁄2-20A); 300Vdc (30 & 60A only)
Amps: 1⁄2-60A
IR: 100kA RMS Sym. 10kA DC
Agency Information: CE, Std. 248-5, Class G, UL Listed, Guide JDDZ, File E4273, CSA Certified, Class 1422-01, File 53787.
Features and Benefits
• Current limiting for component protection, providing Class G energy-limitation for branch circuit protection.
• 100kA interrupting rating provides cost-effective branch pcircuit fusing.
• Variations in length help prevent overfusing.
Typical Applications
• Fusible Branch Panelboards
• HVAC Branch Circuit Protection
General Information:
• Compact branch-circuit units with high interrupting rating and current-limitation.
• With 600V rating, they can be used in 120/208, 120/240 and 277/480V circuits.
• Length variations relative to case size make the “rejection” type fuses.
• In general, SC fuses are about ⁄Ω£ the size of the 600V NEC fuse type.
• SC fuses with ampere ratings above 6A have a degree of overload time-delay which permits them to pass temporary overloads. At 200% load, they have a minimum opening time of 12 seconds.
Dimensions -in (mm)
Fuse Amps | Length | Diameter |
SC-1/2 to 15 | 1.31 (33.3) | 0.41 (10.4) |
SC-20 | 1.41 (35.8) | 0.41 (10.4) |
SC-25 to 30 | 1.62 (41.2) | 0.41 (10.4) |
SC-35 to 60 | 2.25 (57.1) | 0.41 (10.4) |
SC-1/2 | SC-4 | SC-10 | SC-35 |
SC-1 | SC-5 | SC-12 | SC-40 |
SC-1-1/2 | SC-6 | SC-15 | SC-45 |
SC-2 | SC-7 | SC-20 | SC-50 |
SC-2-1/2 | SC-8 | SC-25 | SC-60 |
SC-3 | SC-9 | SC-30 |
Time-Current Characteristic Curves - Average Melt
Current Limitation Curves
Recommended Fuse Holders & Blocks For Class G Fuses
HP Series Fuse Holders
BG Series Fuse Blocks
G Series Fuse Blocks