Description: Advanced protection Class T current -limiting,fast-acting fuses.
Catalog Symbol: JJN-(amp)
Ratings:
Volts: 300Vac (1-10A); 300Vac, 160Vdc (15-600A); 300Vac, 170Vdc (700-1200A)
Amps: 1-1200A
IR: 200kA Vac RMS Sym. 20kA Vdc (15-600A); 100kA Vdc (700-1200A)
Agency Information:
CE, UL Listed, Std. 248-15, Class T, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.15, Class 1422-02, File 53787
Features:
• Small, space-saving fuses provide a high degree of current limitation on short-circuits for excellent component protection
• Commonly applied in electric heat circuits, load center, disconnect switches, and meters
• The small size of the JJN Class T fuses permits installation in panelboards and control centers for system upgrading when existing circuit breakers cannot safely interrupt larger available short-circuit currents
• High speed of response for semiconductor protection
Catalog Numbers (amps)
JJN-1 | JJN-35 | JJN-110 | JJN-400 |
JJN-2 | JJN-40 | JJN-125 | JJN-450 |
JJN-3 | JJN-45 | JJN-150 | JJN-500 |
JJN-6 | JJN-50 | JJN-175 | JJN-600 |
JJN-10 | JJN-60 | JJN-200 | JJN-700 |
JJN-15 | JJN-70 | JJN-225 | JJN-800 |
JJN-20 | JJN-80 | JJN-250 | JJN-1000 |
JJN-25 | JJN-90 | JJN-300 | JJN-1200 |
JJN-30 | JJN-100 | JJN-350 |
Dimensions – in
Fuse Amps | 1-Poles | 2-Pole | 3-Pole | 4-Pole |
½-30 | - | T30030-2_ | T30030-3_ | T30030-4_ |
35-60 | - | T30060-2_ | T30060-3_ | T30060-4_ |
70-100 | - | T30100-1_ | T30100-2_ | T30100-3_ |
110-200 | T30200-1_ | - | - | - |
200 | 1B0083 | - | - | - |
225-400 | T30400-1_ | - | - | - |
450- 600 | T30600-1_ | - | - | - |
Time-Current Curves - Average Melt
Current-Limitation Curves
Current-Limiting Effects
Prosp. S.C.C. Gui | Let-Through Current (Apparent RMS Symmetrical Vs. Fuse Rating) | ||||||||
15A | 30A | 60A | 100A | 200A | 400A | 600A | 800A | 1200A | |
500 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
5000 | 1000 | 1000 | 1000 | 1000 | 2000 | 3000 | 5000 | 5000 | 5000 |
10,000 | 1000 | 1000 | 1000 | 2000 | 2000 | 4000 | 6000 | 7000 | 9000 |
15,000 | 1000 | 1000 | 1000 | 2000 | 3000 | 4000 | 6000 | 9000 | 10,000 |
20,000 | 1000 | 1000 | 1000 | 2000 | 3000 | 5000 | 7000 | 10,000 | 11,000 |
25,000 | 1000 | 1000 | 2000 | 2000 | 3000 | 5000 | 7000 | 10,000 | 12,000 |
30,000 | 1000 | 1000 | 2000 | 2000 | 3000 | 5000 | 8000 | 11,000 | 13,000 |
35,000 | 1000 | 1000 | 2000 | 3000 | 4000 | 6000 | 8000 | 11,000 | 13,000 |
40,000 | 1000 | 1000 | 2000 | 3000 | 4000 | 6000 | 9000 | 11,000 | 13,000 |
50,000 | 1000 | 1000 | 2000 | 3000 | 4000 | 7000 | 9000 | 12,000 | 15,000 |
60,000 | 1000 | 1000 | 2000 | 3000 | 4000 | 7000 | 10,000 | 13,000 | 16,000 |
70,000 | 1000 | 1000 | 2000 | 3000 | 5000 | 7000 | 10,000 | 14,000 | 17,000 |
80,000 | 1000 | 2000 | 2000 | 3000 | 5000 | 8000 | 11,000 | 15,000 | 17,000 |
90,000 | 1000 | 2000 | 2000 | 3000 | 6000 | 8000 | 11,000 | 15,000 | 18,000 |
100,000 | 1000 | 2000 | 2000 | 4000 | 6000 | 8000 | 12,000 | 16,000 | 19,000 |
150,000 | 1000 | 2000 | 3000 | 4000 | 6000 | 9000 | 13,000 | 17,000 | 22,000 |
200,000 | 2000 | 2000 | 3000 | 4000 | 7000 | 9000 | 15,000 | 19,000 | 23,000 |
Custom Designs
Printed circuit board versions available up to 60 amps.
Dimensions - in
PN | A | B |
JJN-1L | 0.406 | 0.125 |
JJN-2L | ||
JJN-3L | ||
JJN-6L | ||
JJN-10L | ||
JJN-15L | ||
JJN-20L | ||
JJN-25L | ||
JJN-30L | ||
JJN-35L | 0.563 | 0.125 |
JJN-40L | ||
JJN-45L | ||
JJN-50L | ||
JJN-60L | ||
JJN-35L-01 | 0.563 | 0.165 |
JJN-40L-01 | ||
JJN-45L-01 | ||
JJN-50L-01 | ||
JJN-60L-01 |
The JJN-XXL products are UL Component Recognized under Guide JFHR2, File E56412.