Description: Time-delay fuse - 4 seconds (minimum) at 500% rated amps.
Ratings:
Volts: 600Vac (or less); 300Vdc (601-2000A)
Amps: 601-6000A (use KRP-CL for current ratings under 601A)
IR: 300kA RMS Sym. 100kA DC
Agency Information: CE, UL Listed- Special Purpose (meets all performance requirements of UL Standard 248-10 for Class L fuses),Guide JFHR, File E56412, CSA Certified (200k AIR), Class 1422-02, File 53787, Class L per CSA C22.2, No. 248.10.
Features and Benefits
• Time delay of four seconds at five times rating allows closer sizing on large motor loads combined with Class L current limitation.
• Selective coordination ratio of 2:1 (within Low-Peak fuse family) prevents electrical shutdowns from extending beyond the failed circuit.
• Interrupting rating of 300kA RMS symmetrical provides adequate ratings without obsolescence for all electrical systems, big or small.
• Quality construction, using high-grade materials, provides lower watts loss and operating temperatures with superior arc quenching during current-limiting action.
General Information:
• All purpose silver-linked fuse for both overload and short-circuit protection for high capacity systems (mains and large feeders).
• Time-delay (minimum of four seconds at five times amp rating) for close sizing.
• Current-limiting action of the fuse generally affords considerable reduction in bus bracing.
• Interrupting rating of 300,000 amperes complies with NEC Sections 110-9 and 230-65 for today’s large capacity systems.
• O-ring seals maximize pressure build-up during current-limiting action and ensure filler retention.
• High grade silica-sand filler; accelerates response of fuse to short-circuits by having quenching effect upon the fuse arc.
• 99.9% pure silver fuselinks. The high conductivity of silver gives low watt loss and low operating temperature at normal current levels; maximizes total clearing I2t fault energy let-through.
• Selective coordination (blackout prevention)
• Glass melamine tube.
• Silver-plated end bells.
Typical Applications
• Large Distribution Switchboards
• Power Panelboards
• Large Machinery Disconnects
Ampere Ratings†
Catalog Number | Ctn. Qty. | Weight** Lbs. | |
Lbs. | Kg. | ||
KRP-C-601SP | 1 | 3.75 | 1.7 |
KRP-C-650SP | |||
KRP-C-700SP | |||
KRP-C-750SP | |||
KRP-C-800SP | |||
KRP-C-801SP | 1 | 4.5 | 2.041 |
KRP-C-900SP | |||
KRP-C-1000SP | |||
KRP-C-1100SP | |||
KRP-C-1200SP | |||
KRP-C-1350SP | 1 | 6.5 | 2.948 |
KRP-C-1400SP | |||
KRP-C-1500SP | |||
KRP-C-1600SP | |||
KRP-C-1800SP | 1 | 8.5 | 3.85 |
KRP-C-1900SP | |||
KRP-C-2000SP | |||
KRP-C-2001SP | 1 | 17.25 | 7.824 |
KRP-C-2400SP | |||
KRP-C-2500SP | |||
KRP-C-3000SP | 1 | 18.25 | 8.278 |
KRP-C-3500SP | 1 | 23.5 | 10.659 |
KRP-C-3800SP | |||
KRP-C-4000SP | |||
KRP-C-4500SP | 1 | 29 | 13.154 |
KRP-C-5000SP | |||
KRP-C-6000SP | 1 | 36 | 16.329 |
†Special purpose rating of 300,000 AIR.
**Weight per carton.
Dimensional Data
601-2000A
Time-Current Characteristic Curves-Average Melt
Current-Limitation Curves
Fuseblocks: (601 - 1200 Amps)
Catalog Number | Poles |
51215 | 1 |
51235 | 3 |
No reducers available. |