Electronic Supply by Industrial Electronics in Milwaukee Wisconsin : Potter Brumfield, Radio Shack Stores in Milwaukee: KRP-C_SP Class L Low-Peak® Time-delay Fuses KRP-C_SP Class L Low-Peak® Time-delay Fuses ================================================================================ synscon on 03/06/2015 10:30:00 Description: Time-delay fuse - 4 seconds (minimum) at 500% rated amps. Ratings: Volts: 600Vac (or less); 300Vdc (601-2000A) Amps: 601-6000A (use KRP-CL for current ratings under 601A) IR: 300kA RMS Sym. 100kA DC Agency Information: CE, UL Listed- Special Purpose (meets all performance requirements of UL Standard 248-10 for Class L fuses),Guide JFHR, File E56412, CSA Certified (200k AIR), Class 1422-02, File 53787, Class L per CSA C22.2, No. 248.10. Features and Benefits * Time delay of four seconds at five times rating allows closer sizing on large motor loads combined with Class L current limitation. * Selective coordination ratio of 2:1 (within Low-Peak fuse family) prevents electrical shutdowns from extending beyond the failed circuit. * Interrupting rating of 300kA RMS symmetrical provides adequate ratings without obsolescence for all electrical systems, big or small. * Quality construction, using high-grade materials, provides lower watts loss and operating temperatures with superior arc quenching during current-limiting action. General Information: * All purpose silver-linked fuse for both overload and short-circuit protection for high capacity systems (mains and large feeders). * Time-delay (minimum of four seconds at five times amp rating) for close sizing. * Current-limiting action of the fuse generally affords considerable reduction in bus bracing. * Interrupting rating of 300,000 amperes complies with NEC Sections 110-9 and 230-65 for today’s large capacity systems. * O-ring seals maximize pressure build-up during current-limiting action and ensure filler retention. * High grade silica-sand filler; accelerates response of fuse to short-circuits by having quenching effect upon the fuse arc. * 99.9% pure silver fuselinks. The high conductivity of silver gives low watt loss and low operating temperature at normal current levels; maximizes total clearing I2t fault energy let-through. * Selective coordination (blackout prevention) * Glass melamine tube. * Silver-plated end bells. Typical Applications * Large Distribution Switchboards * Power Panelboards * Large Machinery Disconnects Ampere Ratings† Catalog Number Ctn. Qty. Weight** Lbs. Lbs. Kg. KRP-C-601SP 1 3.75 1.7 KRP-C-650SP KRP-C-700SP KRP-C-750SP KRP-C-800SP KRP-C-801SP 1 4.5 2.041 KRP-C-900SP KRP-C-1000SP KRP-C-1100SP KRP-C-1200SP KRP-C-1350SP 1 6.5 2.948 KRP-C-1400SP KRP-C-1500SP KRP-C-1600SP KRP-C-1800SP 1 8.5 3.85 KRP-C-1900SP KRP-C-2000SP KRP-C-2001SP 1 17.25 7.824 KRP-C-2400SP KRP-C-2500SP KRP-C-3000SP 1 18.25 8.278 KRP-C-3500SP 1 23.5 10.659 KRP-C-3800SP KRP-C-4000SP KRP-C-4500SP 1 29 13.154 KRP-C-5000SP KRP-C-6000SP 1 36 16.329 †Special purpose rating of 300,000 AIR. **Weight per carton. Dimensional Data 601-2000A 2001-6000A Time-Current Characteristic Curves-Average Melt Current-Limitation Curves Fuseblocks: (601 - 1200 Amps) Catalog Number Poles 51215 1 51235 3 No reducers available.